Whether a circuit will actually disconnect in time ZS
A Type C breaker tolerates half the loop impedance a Type B does. Swapping one in to stop nuisance tripping can leave a circuit that no longer disconnects.
The circuit
The cable
The resistance per metre is yours, from your copy of the tables. The list here is a convenience and is meant to be checked: a figure invented by a web page could size a cable that burns.
Whether it disconnects
The same rating in three types
The working
How it works
ZS checks whether a circuit will disconnect in time under fault, from its earth fault loop impedance. It gives the maximum Zs, applies the 0.8 rule and says how long the run may be. The figures stay in this tab.
Questions people ask about ZS
Where does the maximum loop impedance come from?
From a division, not a table. The device has to see enough current to operate in the required time, and for a circuit breaker the standard fixes that current as a multiple of the rating: five times for a Type B, ten for a Type C, twenty for a Type D. So the maximum loop impedance is the voltage divided by that current, and it falls straight out. For a fuse there is no fixed multiple, so you give the current from its curve.
Which way round does the 0.8 rule go?
A reading taken on a cold circuit is compared against 0.8 of the tabulated figure. The table assumes conductors at their operating temperature, where their resistance is higher, so a cold measurement flatters the circuit. Applying the 0.8 to the measurement rather than to the limit is the common mistake and it passes circuits that fail under load.
Why does the page say how long the run may be?
Because that is the question being asked on site, and no table answers it. Loop impedance is the external figure plus the cable, and the cable is length times resistance per metre, so rearranging gives the length at which the circuit stops disconnecting. It is one line of algebra and it turns a pass or fail into a number you can design to.
What is the adiabatic check for?
A circuit can disconnect in time and still destroy its earth conductor doing it. The protective conductor has to carry the fault current for as long as it takes, and the minimum size is the square root of the current squared times the time, divided by k. A circuit that passes on loop impedance and fails here is a real and quiet failure.
Why are the cable figures not built in?
Because they would be a guess dressed as a fact. Resistance per metre depends on the cable and the table you work to, the figures are revised, and a number invented by a web page and trusted for a year is worse than an empty box. The method here is exact; the data is yours.