Whether a cable is big enough, on both counts VOLTDROP
Four circuits bunched in a warm loft is not the worse of the two factors. It is both of them multiplied, and a cable at 94% of its rating should be at 75%.
The circuit
Three per cent for lighting and five for everything else is the ordinary pair, which on 230 V is 6.9 V and 11.5 V.
The cable, and what is done to it
The tabulated rating and the millivolts per amp per metre are yours, for your cable and your method of installation. They are not invented here: a capacity invented by a web page is a cable that overheats behind a wall.
Whether it passes
The working
How it works
VOLTDROP checks whether a cable is big enough on both counts: current-carrying capacity after correction factors, and voltage drop over the run. Correction factors for grouping and temperature multiply, so a few circuits bunched in a warm loft can overload a cable that looks fine. It compares the cable with the protective device and gives the longest run allowed. The figures stay in this tab.
Questions people ask about VOLTDROP
Why multiply the correction factors?
Because each of them describes a different thing being done to the cable and they all happen at once. Four circuits bunched together and a warm loft is not the worse of the two, it is both: 0.94 for the ambient and 0.80 for the grouping is 0.752, not 0.80. Taking the worst is the common shortcut and it leaves a cable at ninety-four per cent of its rating when it should be at seventy-five.
Why compare the cable with the device and not the load?
Because the device is what decides how much current the cable can be made to carry before anything stops it. A 32 A breaker will pass 32 A indefinitely whatever the intended load is, so the derated capacity has to reach the device’s rating. Sizing to the design current and protecting with something bigger is how a cable ends up unprotected.
Why is volt drop a separate test?
Because it is a different failure. Heat is about how much current the cable can carry; volt drop is about what arrives at the far end. A cable can sit comfortably inside its derated rating over a long run and deliver a voltage the equipment will not start on, and nothing about the first test would ever catch it.
What is the longest run figure?
The length at which volt drop reaches its limit, at this current with this cable. It is the number that actually constrains a long circuit, and it is a rearrangement rather than a table: the limit in millivolts, over the millivolts per amp per metre times the design current.
Why not build in the cable tables?
Because a capacity invented by a web page is a cable that overheats behind a wall. The ratings depend on the cable, the method of installation, the reference temperature and the edition of the table, and they are revised. The method on this page is exact and shown; the data is yours.
Doing this often? Foundry, the Engineering Suite's drawing half draws the cable runs to scale, with dimensions, and prints a PDF to scale or saves DXF. On its own, US$2 a month; with everything else, US$5 a month or US$48 a year.