The room

The working plane is the height the light has to arrive at: 0.85 m for a desk, 0.0 for a floor, higher for a bench. The mounting height the room index uses is measured from there, not from the floor.

The fitting, and the two factors

The utilisation factor comes from the fitting’s own table, read against the room index and the reflectances of the ceiling, walls and floor. The target illuminance comes from the table for the task. Neither is invented here.

The layout

Step by step

The working


    
How it works

LUX works out how many light fittings a room needs to reach a target light level. It uses the utilisation factor, which can vary from under a third in a tall dark room to over two thirds in a low white one, and designs for a room as it will be once dirty. It gives the number of fittings and checks the spacing against the mounting height. The figures stay in this tab.

Questions people ask about LUX

What is the utilisation factor?

The share of a fitting’s light that ever reaches the working plane. The rest goes into the walls, the ceiling and the floor and mostly stays there. In a tall narrow room with dark surfaces it can be under a third; in a low wide white one it can be over two thirds. A design that leaves it out is out by a factor of two and the room is dim on the day it opens.

Why design for a dirty room?

Because the room will be dirty for most of its life and bright for a month. The maintenance factor accounts for lamps depreciating, fittings collecting dust and surfaces getting dirtier, and designing at 0.8 means the room is a little over-lit when new and correct for the years after that. A room that reads exactly its target on handover is under it within a year.

Why is the mounting height measured from the working plane?

Because the room index describes the shape of the space the light has to cross, and the light does not have to cross the last 0.85 m to the floor if the desk is there. Measuring from the floor makes the room look taller than it is, which reads the wrong utilisation factor out of the table and undersizes the installation.

What is the spacing to height ratio for?

It is the furthest apart fittings may be, relative to their height above the plane, before the floor starts to band bright and dim between them. Meeting the average lux while failing the spacing gives a room with the right number on a meter and visible stripes, so the page checks it separately.

Why show what it delivers rather than what was asked for?

Because a fitting is a whole number and a grid is a whole number twice over. The equation asks for 8.4 fittings and the room gets nine in a three by three, which delivers more than the target. Saying so is more useful than repeating the target back.